Fire, electrical & security compliance07517 806082
Get a quote

Guide · Emergency lighting

Emergency lighting testing: monthly and annual checks

What the monthly flick test and annual duration test involve, who can do them, and what to record.

Emergency exit sign and lighting in a dark corridor

Updated 5 November 2026

Quick answer

BS 5266-1 recommends a short monthly functional test of every emergency light and exit sign, and an annual test for the full rated duration, usually three hours. Results and defects should be recorded in a logbook.

Monthly test

  • Simulate a mains failure with a test key switch
  • Check every fitting and sign lights up
  • Restore power and check the charging indicator
  • Record the result and any failed fittings

Annual test

Every fitting runs on battery for its full rated duration, typically three hours. Fittings that fail to last are recorded and replaced. Because the batteries need time to recharge afterwards, the annual test is usually done out of hours or in sections.

Common faults

  • Red or no charging LED: battery, charger or supply fault
  • Fitting fails the duration test: battery near the end of its life
  • Exit sign dim or damaged
  • Fittings missing after refurbishment or alterations

Questions we get asked

Who can do the monthly test?

A trained member of staff or managing agent can do it. We provide simple training and logbooks.

How long do emergency light batteries last?

Often around four years, depending on the type and temperature.

Need this done?

Tell us the address and what you need, or send a photo. We reply quickly with a clear written quote, covering across Lancashire, Greater Manchester and Merseyside.

Get a free quote Call 07517 806082

From our recent jobs

Photos from our own jobs. Codes, people and other firms' details are blurred.

Three-phase distribution board with dedicated fire alarm and emergency lighting circuits
Three-phase distribution board with dedicated, labelled fire alarm and emergency lighting circuits.
Smoke vent controller and smoke vent break-glass on a communal landing
Smoke vent (AOV) controller and smoke vent break-glass on a communal landing.

Need a certificate, a repair or a quote?

Tell us the address and what you need. We reply the same working day.