Quick answer
Smoke control should have a short routine test by building staff (commonly weekly or monthly) and a full service by a competent engineer at least once a year. Many blocks of flats, and any building where the system is critical to escape, are serviced every six months.
Why answers differ
Guidance such as BS 9999 and BS 7346-8 sets minimums, and manufacturers add their own recommendations. Some contractors quote the annual minimum and others recommend six-monthly visits. Both can be right: the correct interval depends on the building, how critical the system is to escape, and its condition.
Routine tests by building staff
- Trigger the system from a break-glass or test switch (rotate the point used each time)
- Check each vent opens fully and closes again on reset
- Check the panel shows normal and no fault LEDs
- Record the date, the point used and the result in the fire log book
Professional servicing
A competent engineer tests every trigger and output, load-tests the batteries, checks actuators, dampers and fans, verifies the fire alarm interface and weather controls, and issues a written report. This is the visit that finds problems before they cause a failure.
Choosing your interval
| Building | Typical servicing interval |
|---|---|
| Low-rise block, simple stair-head vent | Annual, with routine user tests |
| Mid or high-rise residential, stay-put strategy | Six-monthly |
| Smoke shafts and mechanical extract | Six-monthly, plus monthly fan run tests |
| System with a history of faults | Six-monthly until it is reliable |
| Commercial building, AOV used for ventilation | Annual or six-monthly depending on use |
Your fire risk assessment should confirm the interval. If it doesn't mention the smoke control system, ask your assessor to include it.
Related services
Related guides
Questions we get asked
Who can carry out the weekly or monthly test?
A trained member of staff, caretaker or managing agent can carry out the routine user test. The full service should be done by a competent engineer.
What records should I keep?
Keep the routine test log, every service report and records of repairs. These show the system has been maintained and are needed for your building safety file.
Need this done?
Tell us the address and what you need, or send a photo. We reply quickly with a clear written quote, covering anywhere in the UK.
From our recent jobs
Photos from our own jobs. Codes, people and other firms' details are blurred.


Manufacturers we work with
We install, service and repair equipment from all of these manufacturers. The most relevant for this page are shown first.
Need a certificate, a repair or a quote?
Tell us the address and what you need. We reply the same working day.