Fire, electrical & security compliance07517 806082
Get a quote

Guide · Smoke control

How often should AOVs be tested and serviced?

Contractors give different answers, from once a year to every six months. Here's how routine tests and professional servicing fit together, and how to choose the right interval for your building.

Automatic smoke vent open on the roof of an apartment block

Updated 5 November 2026

Quick answer

Smoke control should have a short routine test by building staff (commonly weekly or monthly) and a full service by a competent engineer at least once a year. Many blocks of flats, and any building where the system is critical to escape, are serviced every six months.

Why answers differ

Guidance such as BS 9999 and BS 7346-8 sets minimums, and manufacturers add their own recommendations. Some contractors quote the annual minimum and others recommend six-monthly visits. Both can be right: the correct interval depends on the building, how critical the system is to escape, and its condition.

Routine tests by building staff

  • Trigger the system from a break-glass or test switch (rotate the point used each time)
  • Check each vent opens fully and closes again on reset
  • Check the panel shows normal and no fault LEDs
  • Record the date, the point used and the result in the fire log book

Professional servicing

A competent engineer tests every trigger and output, load-tests the batteries, checks actuators, dampers and fans, verifies the fire alarm interface and weather controls, and issues a written report. This is the visit that finds problems before they cause a failure.

Choosing your interval

BuildingTypical servicing interval
Low-rise block, simple stair-head ventAnnual, with routine user tests
Mid or high-rise residential, stay-put strategySix-monthly
Smoke shafts and mechanical extractSix-monthly, plus monthly fan run tests
System with a history of faultsSix-monthly until it is reliable
Commercial building, AOV used for ventilationAnnual or six-monthly depending on use

Your fire risk assessment should confirm the interval. If it doesn't mention the smoke control system, ask your assessor to include it.

Questions we get asked

Who can carry out the weekly or monthly test?

A trained member of staff, caretaker or managing agent can carry out the routine user test. The full service should be done by a competent engineer.

What records should I keep?

Keep the routine test log, every service report and records of repairs. These show the system has been maintained and are needed for your building safety file.

Need this done?

Tell us the address and what you need, or send a photo. We reply quickly with a clear written quote, covering anywhere in the UK.

Get a free quote Call 07517 806082

From our recent jobs

Photos from our own jobs. Codes, people and other firms' details are blurred.

Smoke vent controller and smoke vent break-glass on a communal landing
Smoke vent (AOV) controller and smoke vent break-glass on a communal landing.
Roof window and flashing on a slate roof
Roof window and flashing on a slate roof.

Need a certificate, a repair or a quote?