Fire, electrical & security compliance07517 806082
Get a quote

AOV actuators · UK-wide

AOV actuator and window motor replacement

Failed chain actuators, linear actuators and window motors replaced and set up so the vent opens to its full design area, then tested from every trigger.

Smoke vent controller and smoke vent break-glass on a communal landing

In short

An actuator is the motor that physically opens the smoke vent. When one fails, the replacement must match the stroke, force and speed the vent was designed for, otherwise the vent may not open far enough to clear smoke.

Signs an actuator has failed

  • The panel shows an alarm but the vent doesn't move
  • The motor hums or clicks but the chain doesn't extend
  • The vent opens only part of the way, or opens and immediately closes
  • Visible damage: a snapped chain, sheared bracket or water inside the housing

Matching the replacement

We check the window size, weight, hinge position and required opening angle, then fit an actuator with the right stroke and push force. Where the original is still available we fit like for like. Where it isn't, we fit a compatible model and adjust the brackets so the vent still opens to its full free area.

Large or heavy vents may need twin actuators running together. These must be synchronised so the window doesn't twist on its hinges.

After fitting

Every replaced actuator is tested from the panel, the break-glass, the detectors and the fire alarm interface (where fitted), and on battery power alone. You get a short report confirming the vent opens and closes correctly.

Questions we get asked

Can one actuator be replaced on its own?

Yes, if the rest of the system is healthy. If several actuators are the same age and failing, it can be cheaper to replace them together in one visit.

Do you fit actuators on rooflights as well as windows?

Yes. We replace actuators on side-hung and top-hung windows, roof vents and rooflights.

Need this done?

Tell us the address and what you need, or send a photo. We reply quickly with a clear written quote, covering anywhere in the UK.

Get a free quote Call 07517 806082

From our recent aov & smoke control jobs

Photos from our own jobs. Codes, people and other firms' details are blurred.

Smoke vent controller and smoke vent break-glass on a communal landing
Smoke vent (AOV) controller and smoke vent break-glass on a communal landing.
Roof window and flashing on a slate roof
Roof window and flashing on a slate roof.
Smoke vent control point being tested: open and close