Fire safety
AOVs and smoke ventilation explained
Automatic smoke vents that clear smoke from stairs and corridors so people can escape.
In plain English
An AOV (automatic opening vent) is a window, roof vent or shaft damper that opens by itself when smoke is detected. It lets smoke and heat out of a stairwell or corridor so the escape route stays clear and firefighters can see.
What the law says
Building Regulations — Approved Document B
New and refurbished blocks of flats normally need smoke ventilation to the common corridors and stairs. Once fitted, it must not be removed or disabled.
Regulatory Reform (Fire Safety) Order 2005
The responsible person must keep smoke ventilation in efficient working order and good repair.
Fire Safety (England) Regulations 2022
In residential buildings 18 metres or taller, smoke control is 'essential firefighting equipment': it must be checked monthly, and faults not fixed within 24 hours must be reported to the fire service.
Standards we work to
- BS EN 12101-2 — Product standard for natural smoke and heat exhaust ventilators (the vents themselves).
- BS EN 12101-10 — Standard for the power supplies that run smoke control systems.
- BS 9991 / BS 9999 — Design codes for fire safety in residential and other buildings, including how smoke ventilation should work and be maintained.
Who is responsible?
The building owner, freeholder, management company or managing agent responsible for the common parts.
The components we install
These are the parts that make up a typical aovs and smoke ventilation installation, what each one does, and what a healthy one looks like.
Smoke vent / AOV window
The opening itself — a window, louvre or roof vent sized to let enough smoke out.
What to look for: Opens fully, not painted shut, not blocked by furniture or bars.
Chain actuator
A motor with a stiff chain that pushes the window open. The most common type on stairwell windows.
What to look for: Chain runs smoothly, brackets tight.
Linear (spindle) actuator
A piston-style motor used for heavier vents and roof lights.
What to look for: No grinding, seals intact.
Smoke control panel
Powers the actuators, holds the batteries and decides when to open or close the vents.
What to look for: Green healthy light, no faults or buzzer.
Standby batteries
Keep the vents working in a power cut. Usually replaced every 4 years.
What to look for: Dated label in the panel.
Smoke detector
Usually one on each floor landing. Triggers the vents when it senses smoke.
What to look for: Not covered or painted.
Firefighter override switch
A key or break-glass switch at the ground floor that lets firefighters open or close vents.
What to look for: Labelled 'Fire service use only', unobstructed.
Vent open/close switch
A local switch for daily ventilation or testing.
What to look for: Returns vents to closed after use.
Weather (wind/rain) sensor
Closes vents used for everyday ventilation when it rains — but never overrides a fire signal.
What to look for: Clean, not damaged.
Smoke shaft and damper
In some blocks, smoke goes into a dedicated shaft through a damper on each floor.
What to look for: Damper opens on the fire floor only.
How often it must be checked
- Weekly or monthlyOperate the system (often via the fire alarm test) and check vents open and close.By: Site staff or us
- Monthly (18m+ buildings)Recorded check of smoke control as essential firefighting equipment.By: Responsible person
- At least yearlyFull service: actuators, control panel, batteries, detectors, switches and vent operation tested and certified.By: Competent AOV engineer
Paperwork you should get
- Commissioning certificate — Shows the system was set up and tested as designed.
- Service certificate / report — Issued after each service, listing faults and recommended repairs.
- O&M manual — Operation and maintenance manual describing the system, wiring and parts.
Simple checks you can do
- Look at the panel each week for faults.
- Make sure nobody has fitted locks, bars or blinds that stop vents opening.
- Report broken actuator chains or windows left open at once.
- In 18m+ buildings, record the monthly check.
Common questions
Can a smoke vent also be used for fresh air?
Yes, many are dual-purpose, with a switch and a weather sensor. In a fire the smoke signal always takes priority.
The vent opens but won't close. Is that dangerous?
It's a fault that needs fixing quickly — it can let rain in and stop the system resetting. Call us and we'll attend.
Do you cover my area?
Yes — AOV work is covered UK-wide.
Need this installed, tested or certified?
We install, service and certify this equipment and hand you every certificate in plain English.
Related guides
This guide is a plain-English summary to help you understand your duties. It is not legal advice, and rules can change. Your fire risk assessment, insurer or local council may ask for more.
Manufacturers we work with
We install, service and repair equipment from all of these manufacturers. The most relevant for this page are shown first.
Need a certificate, a repair or a quote?
Tell us the address and what you need. We reply the same working day.