How often does everything need testing?

One page with every check, test and service interval for the systems we install — who does it and how often.

Tip: put every date in one calendar. Missed tests are the most common thing fire officers, councils and insurers pick up on.

Fire alarm systems

  • WeeklySet off one manual call point and check the sounders work. Use a different call point each week and write it in the log book.By: You or your staff
  • Every 6 months (max)Full inspection and service: detectors tested, batteries checked, panel and faults checked, certificate issued.By: Competent fire alarm engineer
  • YearlyOver each 12 months, every detector and call point should have been tested at least once (often split across the two services).By: Competent fire alarm engineer

Emergency lighting

  • MonthlyA short 'flick test': cut the power to the lights briefly and check every emergency fitting comes on.By: You, your staff or us
  • YearlyFull duration test: run the lights on battery for their full rated time (usually 3 hours) and check none dim or fail.By: Competent electrician

AOVs and smoke ventilation

  • Weekly or monthlyOperate the system (often via the fire alarm test) and check vents open and close.By: Site staff or us
  • Monthly (18m+ buildings)Recorded check of smoke control as essential firefighting equipment.By: Responsible person
  • At least yearlyFull service: actuators, control panel, batteries, detectors, switches and vent operation tested and certified.By: Competent AOV engineer

Smoke, heat and CO alarms in homes

  • Start of every tenancyLandlord checks each alarm works on day one.By: Landlord or agent
  • MonthlyPress the test button on each alarm.By: Occupier
  • Every 10 yearsReplace smoke and heat alarms (date is on the side). CO alarms usually last 5–10 years — check the label.By: Landlord / homeowner

Fire doors

  • Every 3 monthsCheck communal fire doors in blocks over 11 m.By: Responsible person or inspector
  • Every 12 monthsCheck flat entrance doors in blocks over 11 m; full survey recommended in most other buildings.By: Competent fire door inspector
  • Every 6 months (busy doors)Heavy-use doors in schools, hospitals and offices need more frequent checks.By: Competent fire door inspector

Fire extinguishers and blankets

  • MonthlyQuick look: in place, pin and seal intact, gauge in the green, not damaged.By: You or your staff
  • YearlyBasic service and service label updated.By: Competent extinguisher engineer
  • Every 5 yearsExtended service (discharge test and refill) for water, foam and powder.By: Competent engineer
  • Every 10 yearsCO2 extinguishers overhauled or replaced.By: Competent engineer

Sprinkler systems

  • Weekly (commercial)Check pressures, water levels, valves, and run pumps.By: Site staff
  • Yearly (minimum)Full service and inspection.By: Competent sprinkler engineer

Dry risers and wet risers

  • Every 6 monthsVisual inspection of inlets, outlets, valves and cabinets.By: Competent engineer
  • YearlyWet test: the riser is filled and pressure tested (typically 12 bar for 15 minutes).By: Competent engineer

Kitchen fire suppression

  • Every 6 monthsService: detection, nozzles, agent, release and gas shut-off tested.By: Competent suppression engineer

Fire stopping and compartmentation

  • After any workCheck that new holes have been sealed with the right product.By: Contractor / site manager
  • Yearly (typical)Compartmentation survey in blocks and HMOs, as the fire risk assessment requires.By: Competent surveyor

Evacuation alert systems

  • Regularly (typically every 6 months)Service and test of the control equipment and alert devices in flats.By: Competent engineer

Electrical installations and EICRs

  • Every 5 years (max)EICR for privately rented homes and most commercial premises.By: Qualified electrician
  • Every 10 yearsRecommended EICR for owner-occupied homes, or when buying a property.By: Qualified electrician
  • More oftenSome premises like swimming pools, caravan parks or industrial sites need shorter intervals.By: Qualified electrician
  • Every 3 monthsPress the 'T' test button on each RCD.By: You

EV chargers

  • YearlyVisual check and functional test (recommended).By: Qualified electrician
  • With your EICRIncluded in the periodic inspection.By: Qualified electrician

Air conditioning

  • YearlyService: filters, coils, drains, refrigerant and electrics checked.By: F-gas certified engineer
  • Yearly or moreLeak check if the system is 5 tonnes CO2 equivalent or more.By: F-gas certified engineer
  • Every 5 yearsTM44 inspection for systems over 12 kW.By: Accredited energy assessor

Automatic barriers and gates

  • Every 6 months (recommended)Service, safety device checks and force test with a calibrated meter.By: Competent gate/barrier engineer
  • Daily/weeklyQuick look: safety beams working, no damage.By: Site staff

CCTV

  • MonthlyCheck every camera has a picture and the recorder is recording with the right time.By: You
  • YearlyService: clean cameras, check hard drive health, firmware, cabling.By: Security engineer

Access control and door entry

  • YearlyService: locks, readers, power supplies, batteries and fire release tested.By: Security engineer
  • WeeklyWith the fire alarm test, check electrically locked doors release.By: Site staff

Intruder alarms

  • Once or twice a yearService: detectors, batteries, sounders and signalling. Twice yearly is required for some non-monitored systems.By: Approved installer
  • MonthlyWalk test and check the panel log.By: You

Nurse call and warden call

  • Daily/weeklyTest sample call points and check the panel log.By: Care staff
  • YearlyFull service of all call points, cords, displays, pagers and batteries.By: Nurse call engineer

Data cabling, Wi-Fi and fibre

  • On installEvery cable certified with a tester, and results handed over.By: Network installer
  • As neededFault finding and re-testing after changes.By: Network installer

Gas appliances and safety checks

  • Every 12 monthsLandlord gas safety check of all appliances and flues.By: Gas Safe registered engineer
  • Every 12 monthsBoiler service (recommended for everyone).By: Gas Safe registered engineer

Need this installed, tested or certified?

We install, service and certify this equipment and hand you every certificate in plain English.

This guide is a plain-English summary to help you understand your duties. It is not legal advice, and rules can change. Your fire risk assessment, insurer or local council may ask for more.

Need a certificate, a repair or a quote?

Tell us the address and what you need. We reply the same working day.