Fire safety
Dry risers and wet risers explained
The empty pipes firefighters connect to so they get water to upper floors fast.
In plain English
A dry riser is an empty vertical pipe running up a tall building. Firefighters pump water into an inlet at ground level and connect hoses to outlets on each floor. A wet riser is the same but is kept full of water, used in very tall buildings.
What the law says
Building Regulations — Approved Document B
Buildings with a floor more than 18 metres up need a firefighting main (dry riser). Above 50 metres it must be a wet riser.
Regulatory Reform (Fire Safety) Order 2005
Firefighting equipment must be maintained.
Fire Safety (England) Regulations 2022
In residential buildings 18 m or taller, risers are essential firefighting equipment: monthly checks, and faults not fixed within 24 hours reported to the fire service.
Standards we work to
- BS 9990 — Code of practice for firefighting mains, including inspection and testing.
Who is responsible?
The building owner or responsible person.
The components we install
These are the parts that make up a typical dry risers and wet risers installation, what each one does, and what a healthy one looks like.
Inlet breeching
The ground-floor box where the fire engine connects. Often behind a glazed door marked 'Dry riser inlet'.
What to look for: Box closed, caps on, signage clear.
Landing valve (outlet)
The outlet on each floor where hoses connect.
What to look for: Valve closed, strapped and padlocked, blank cap fitted.
Riser pipe
The pipe itself, usually galvanised steel.
What to look for: No visible damage.
Air release valve
At the top, lets air out as water goes in.
What to look for: Not blocked.
Drain valve
Empties the pipe after use.
What to look for: Closed.
Cabinets and signs
Protect the valves from vandalism and show firefighters where they are.
What to look for: Undamaged and labelled.
How often it must be checked
- Every 6 monthsVisual inspection of inlets, outlets, valves and cabinets.By: Competent engineer
- YearlyWet test: the riser is filled and pressure tested (typically 12 bar for 15 minutes).By: Competent engineer
Paperwork you should get
- Riser test certificate — Shows pressure test results and any defects.
Simple checks you can do
- Make sure inlets and outlets aren't blocked or vandalised.
- Report missing caps or broken cabinets immediately.
Common questions
Why do they get vandalised?
Brass parts are a target for thieves. Missing parts make the riser useless, so report damage straight away.
Need this installed, tested or certified?
We install, service and certify this equipment and hand you every certificate in plain English.
Related guides
This guide is a plain-English summary to help you understand your duties. It is not legal advice, and rules can change. Your fire risk assessment, insurer or local council may ask for more.
Manufacturers we work with
We install, service and repair equipment from all of these manufacturers. The most relevant for this page are shown first.
Need a certificate, a repair or a quote?
Tell us the address and what you need. We reply the same working day.