Fire safety
Emergency lighting explained
The lights that come on in a power cut so people can find the way out.
In plain English
Emergency lights are fittings with their own battery (or wired to a central battery) that switch on automatically when the normal lighting fails. They light escape routes, stairs, exits and fire equipment so people can get out safely in the dark.
What the law says
Regulatory Reform (Fire Safety) Order 2005
Escape routes and exits that need lighting must have emergency lighting that works if the normal supply fails, and it must be kept in good working order.
Standards we work to
- BS 5266-1 — Code of practice for emergency lighting: where it goes, how it's designed and how often it's tested.
- BS EN 1838 — Sets how bright it must be — for example at least 1 lux along the centre of an escape route and 0.5 lux in open areas.
- BS EN 50172 — Testing and record keeping for emergency escape lighting.
Who is responsible?
The responsible person for the building (owner, employer, landlord or managing agent).
The components we install
These are the parts that make up a typical emergency lighting installation, what each one does, and what a healthy one looks like.
Non-maintained bulkhead
Off normally, comes on only when the power fails. Common on corridors and stairs.
What to look for: Small green charging light lit.
Maintained fitting
On all the time and stays on in a power cut. Used in places like theatres and some HMOs.
What to look for: Lit, not flickering.
Exit sign
The green 'running man' sign showing the way out. Must stay lit in a power cut.
What to look for: Arrow points the right way, clearly visible.
Test key switch
A small key switch that lets you cut power to the lights for testing without switching off the whole circuit.
What to look for: Key kept somewhere safe and known.
Battery pack
Inside each fitting. Usually lasts around 4 years before it can no longer give the full 3 hours.
What to look for: Fitting passes the annual 3-hour test.
Self-test / addressable fittings
Fittings that test themselves and report faults, sometimes to a central panel. Saves monthly hassle.
What to look for: No red fault light on the fitting.
Central battery system
One large battery bank feeding many fittings. Used in big buildings.
What to look for: Room ventilated, no alarms on the cabinet.
External emergency light
Lights the area just outside the final exit so people don't step out into darkness.
What to look for: Weatherproof, working.
How often it must be checked
- MonthlyA short 'flick test': cut the power to the lights briefly and check every emergency fitting comes on.By: You, your staff or us
- YearlyFull duration test: run the lights on battery for their full rated time (usually 3 hours) and check none dim or fail.By: Competent electrician
Paperwork you should get
- Completion / commissioning certificate — Issued when a new system is installed.
- Periodic inspection and test certificate — Issued after the annual full duration test.
- Emergency lighting log book — Monthly and annual tests, faults and repairs recorded.
Simple checks you can do
- Do the monthly flick test and log it.
- Look for fittings with no green charge light.
- Don't block exit signs with stock or displays.
- Book the annual 3-hour test well before the year runs out.
Common questions
Does every home need emergency lighting?
No. Single homes don't. Common parts of flats, many HMOs and all businesses with escape routes usually do — your fire risk assessment will say.
Why 3 hours?
It gives time to evacuate, search the building and get people back in safely. Some low-risk premises use 1 hour, but 3 hours is the normal choice.
Need this installed, tested or certified?
We install, service and certify this equipment and hand you every certificate in plain English.
Related guides
This guide is a plain-English summary to help you understand your duties. It is not legal advice, and rules can change. Your fire risk assessment, insurer or local council may ask for more.
Manufacturers we work with
We install, service and repair equipment from all of these manufacturers. The most relevant for this page are shown first.
Need a certificate, a repair or a quote?
Tell us the address and what you need. We reply the same working day.